Split air conditionerWall mounted TypeService manualAUS-07H53R010Px(X=1,2,3,...)AUS-09H53R150PxAUS-12H53R150PxAUS-12H53R130PxAUS-09H53R010PxMUP-0
BurrObliqueCopper pipe90RoughnessReamerBurr Outer diameter A(mm)2.0--2.53.0--3.53.5--4.06.35mm ( 1/4 )9.52mm ( 3/8 )12.7mm ( 1/2 )15.88mm(5/
Screw the gas shut-off valve to close, connect charging hose(low pressure) to the service valve and then open gas shut-off valve again.Connect the ref
Operation test8Before test operation, wiring safety inspection must be carried out carefully again.1. Emergency switch operation: Every press of emerg
TROUBLE SHOOTING Items to be checked first1. Is the voltage of the power correct? The input voltage shall be rating voltage 10%. The air condit
FAULT DIAGNOSIS BY SYMPTOM No cooling effect at allFan motor errorFan motor or its capacitor faults.Loose connection or badly contact.compressor does
No heating effect at allFan motor errorFan motor or its capacitor faults.Loose connection or badly contact.compressor does not operateControl circuit
Noise from indoor unitCollision sound of the machineFlowing sound of the liquidSound of the running fan motorSound of plastic pieces rubbing or defor
Switching on the air conditioner The current leakage switch jumps to turn off Junction wire looses and collides with the o
CONTROL SPECIFICATION1122ABBREVIATIONST: Setting TemperaturePT: Indoor coil Pipe TemperatureRT: Room TemperatureOT: Outdoor coil pipe temperatureOPERA
HEAT MODEIf the air conditioner is off and then turned on while set at COOL ,HEAT or DRY mode, it will take approximately 3 minutes for the compressor
1 CONTENTS11ContentsSafety precautionsInstallation 1111Block diagram1212Trouble shooting1313Fault diagnosis by symptom1717Control specification2323To
DRY MODEIn this mode, the air conditioner automatically sets the room temperature and this temperatureis incontrollable by remote controller. The init
CONTROL SPECIFICATION20FAN MODEIn this mode, the outdoor unit does not operate. The indoor fan alone operates. Press UP & DOWN SWING button or L
CONTROL SPECIFICATIONWhen 28 st 31 ,the unit will operate at the set temperature all along.When the air conditioner is in heat mode and18 st 16 , t
When the air conditioner is in cooling and dry mode and 23 st 16 , during the 3 hours after sleep mode 3 start up, the set temperature will increase
Stop operation of the air conditioner and remove the power cord before repairing the unit.Indoor unit No Parts Procedure Remark1 Front grille 1.Stop
4.Separate the electrical box from the indoor unit. 1.Loosen the earth screw in evaporator.2.Loosen the sull softly the indoor pipe te
3.Separate the evaporator from the indoor unit.4Evaporator2.Separete the ass’y tray drain from the body.1.Push the left hook and separate the l
Outdoor unit1 Cabinet 1.Turn off the unit and remove the power cable.2.Remove the upper cabinet, the front cabinet and back cabinet.2
Indoor unitExploded Views and Parts List27
Exploded Views and Parts List28Indoor unitNo. English Part Name Quantity No. English Part Name Quantity1Electrical control box with airsensitive dis
The following safety precautions must be taken when using your air conditioner.SAFETY PRECAUTIONS1. Warning: Prior to repair, disconnect the power cor
Outdoor unitExploded Views and Parts List29AUS-09H53R150Px AUS-12H53R150Px MUP-09-HI AND MUP-12-HI
No. English Part Name Quantity No. English Part Name Quantity1 Air outlet grille 1 26 Right handle 12 Front panel 1 27 Outdoor fan motor supporter 1
Wiring DiagramsIndoor unitOutdoor unit31AUS-07H53R010PxAUS-09H53R150PxAUS-12H53R150PxAUS-12H53R130PxAUS-09H53R010PxAUS-07H53R010Px AUS-09H53R010PxFLIF
Wiring DiagramsOutdoor unit32AUS-09H53R150PxAUS-12H53R150PxAUS-12H53R130Px MUP-09-HI AND MUP-12-HI
frontrightbackUndersideLeft-backbackNotice: do not elevate the drain hose.The copper pipe can be ledfrom back, right, underside, or left-back side.Co
INSTALLATION4 Securing the mounting plate and drill on the wall 1Pipe holeCenter of hole( 65mm) Center of hole( 65mm) Drill on the wall Opera
Wiring2Open the front grille;Remove the screw from electrical box cover, pull the electrical box cover away from the unit and set aside.Remove the s
Arrangement of the drain hoseTo drain the condensate water easily, the drain hose should be declined downwards.The following 5 arrangement methods are
INSTALLATIONConnectingcableOutdoor unit terminal1 Wiring1 Remove the self-tapping screws (2 pcs) on the maintenance board and take out the maintenanc
8INSTALLATIONIf the interconnection cord for power supply has to be replaced, please see the following table for reference.Notice: If the signal wire